Protocols and drivers
- Communication
- 1 × RS485 Modbus; 1 × CANopen

KC200 VFD
The Kinco KC200 is a VFD with official catalog ratings of 0.4–2.2 kW at single-phase 200–240 V and 0.75–560 kW at three-phase 380–480 V. It provides six digital inputs, two analog inputs, two relay outputs, RS485 Modbus and CANopen, with an optional 5 V, 12 V or 24 V incremental PG card. Selection remains subject to engineering review of the exact rating, motor and duty.

Lead time confirmed within 1 business day
1business day first reply
| Model | KC200 |
|---|---|
| Single Phase Supply | 200–240 V, -15% to +10%, 50/60 Hz |
| Single Phase Power Range | 0.4–2.2 kW |
| Three Phase Supply | 380–480 V, -15% to +10%, 50/60 Hz |
| Three Phase Power Range | 0.75–560 kW |
| Digital Inputs | 6 |
| Analog Inputs | 2 |
| Relay Outputs | 2 |
| Digital Outputs | 2 |
| Analog Outputs | 2 |
| High Speed Pulse Input | 1, multiplexed with DI6 |
| High Speed Pulse Output | 1, multiplexed with DO2 |
| Communication | 1 × RS485 Modbus; 1 × CANopen |
| Optional Pg Card | 5 V, 12 V or 24 V incremental PG card |
| Motor Scope | three-phase AC asynchronous motors |
| Published Applications | lifting, cement, rubber-tire equipment, industrial water treatment, ventilation, stirring, HVAC cooling and woodworking |
| Inverter model | Power capacity (kVA) | Input current (A) | Output current (A) | Adaptive motor (kW) |
|---|---|---|---|---|
| Single-phase 200–240V, 50/60Hz | ||||
| KC200-2S-0R40G | 1 | 5.3 | 2.5 | 0.4 |
| KC200-2S-0R75G | 1.5 | 8.2 | 4 | 0.75 |
| KC200-2S-01R5G | 3 | 14 | 7.5 | 1.5 |
| KC200-2S-02R2G | 4 | 23 | 10 | 2.2 |
| Three-phase 380–480V, 50/60Hz | ||||
| KC200-4T-0R75G | 1.5 | 3.4 | 2.3 | 0.75 |
| KC200-4T-01R5G | 2.5 | 5 | 3.7 | 1.5 |
| KC200-4T-02R2G | 3.6 | 5.8 | 5.5 | 2.2 |
| KC200-4T-03R7G | 5.8 | 10.5 | 8.8 | 3.7 |
| KC200-4T-05R5G | 8.6 | 14.5 | 13 | 5.5 |
| KC200-4T-07R5G | 11 | 20.5 | 17 | 7.5 |
| KC200-4T-0011G | 16.5 | 26 | 25 | 11 |
| KC200-4T-0015G | 21 | 35 | 32 | 15 |
| KC200-4T-0018G | 24.5 | 38.5 | 37 | 18.5 |
| KC200-4T-0022G | 29.5 | 46.5 | 45 | 22 |
| KC200-4T-0030G | 39.5 | 62 | 60 | 30 |
| KC200-4T-0037G | 49.5 | 76 | 75 | 37 |
| KC200-4T-0045G | 59 | 92 | 90 | 45 |
| KC200-4T-0055G | 72.5 | 113 | 110 | 55 |
| KC200-4T-0075G | 100 | 157 | 152 | 75 |
| KC200-4T-0090G | 116 | 180 | 176 | 90 |
| KC200-4T-0110G | 138 | 260 | 210 | 110 |
| KC200-4T-0132G | 166 | 232 | 252 | 132 |
| KC200-4T-0160G | 200 | 282 | 304 | 160 |
| KC200-4T-0185G | 230 | 326 | 350 | 185 |
| KC200-4T-0200G | 250 | 352 | 380 | 200 |
| KC200-4T-0220G | 280 | 385 | 426 | 220 |
| KC200-4T-0250G | 309 | 437 | 470 | 250 |
| KC200-4T-0280G | 342 | 491 | 520 | 280 |
| KC200-4T-0315G | 395 | 580 | 600 | 315 |
| KC200-4T-0355G | 437.5 | 624 | 665 | 355 |
| KC200-4T-0400G | 629 | 670 | 725 | 400 |
| KC200-4T-0450G | 715 | 792 | 820 | 450 |
| KC200-4T-0500G | 800 | 835 | 950 | 500 |
| KC200-4T-0560G | 896 | 920 | 1020 | 560 |
Source: Kinco General Catalog 202510, printed page 34 (PDF page 19), 'KC200 series inverter specifications and technical parameters'.
| Model number | KC200 |
|---|---|
| Brand | Kinco |
| Category | VFD Drives |
| Availability | Typically in stock, quantity and lead time confirmed at RFQ |
The official catalog lists single-phase 200–240 V models from 0.4 to 2.2 kW, three-phase 380–480 V models from 0.75 to 560 kW, standard RS485 Modbus and CANopen communication, and an optional 5 V, 12 V or 24 V incremental PG card.
KC200 may be considered as a candidate replacement — subject to engineering review. The incumbent application and this product's published specifications must be reviewed before selection.
Send the application, quantity and target date. We will check fit and availability.
We check the motor, supply, load, braking and protocol before selecting the KC200.
The cited official catalog page confirms voltage classes, power ranges, terminal counts, Modbus, CANopen and optional incremental PG cards, but does not publish the control method, overload curve, braking provision, ingress protection, temperature range or certification status
those fields remain confirmed during engineering review
The 0.4–560 kW range spans many frames, so dimensions and current ratings must be checked against the exact order code
A line-by-line BOM review checks the whole list against the application before it becomes an order.